E260 N/2/1 - N12/2 and E260 N32/2 - N32/8 emergency power control are central devices operating many smoke extraction systems.

RWA center control and supplies with energy devices of the smoke extraction system. Depending on the type of RWA center, there is a change in maximal output current supplying drives and number of ventilating groups.

Center-to-network BUS MBZ300 - modular, flexible and easy to operate. It is possible to easily expand the MBZ300 center and adjust it to individual building needs. The center controls all the functions of the RWA system not only in case of fire but also in everyday building ventilation. Additional indicators on the module facilitate the installation and maintenance.

Product properties:

  • Supply voltage 230 V AC 50 Hz.
  • Output voltage 24 V (20-30 V) DC, residual sinusoid < 20%.
  • Voltage backup for at least 72 hours with 2 lead batteries 12 V.
  • All functions maintained also at battery operation.
  • Alarm erase from smoke detector with RESET button.
  • LED indicators of operating status and damage.
  • VdS certificate.

Possibilities to connect external devices:

  • Up to eight groups of drives.
  • Up to 15 buttons FT 4-24 V DC.
  • Up to 20 smoke or temperature detectors.
  • For each group - three ventilating buttons with LEDs / any number of ventilating buttons without LEDs.
  • Potential-free signal contact: three alarm contacts (sound), damage (light), and window opening.

Product properties:

  • Supply voltage 230 V AC 50 Hz.
  • Output voltage 24 V (20-30 V) DC, residual sinusoid < 20%.
  • Voltage backup for at least 72 hours with 2 lead batteries 12 V.
  • All functions maintained also at battery operation.
  • Alarm erase from smoke detector with RESET button.
  • LED indicators of operating status and damage.
  • VdS certificate.

Possibilities to connect external devices:

  • Up to four groups of drives, depending on the center type.
  • Up to 10 smoke or temperature detectors.
  • Up 20 smoke extraction buttons FT4- 24 V DC.
  • For each group - three ventilating buttons with LEDs / any number of ventilating buttons without LEDs.
  • Potential-free signal contact: three alarm contacts (sound), damage (light), and window opening.

Product properties:

  • Easy and convenient center’s expansion with modules embedded with clips.
  • Possibility to expand the center with additional alarm and ventilating groups as well as alarm lines.
  • Possibility to create networks with additional centers and creation of a full system.
  • Imaging of a full alarm scenario.
  • Easy installation and maintenance thanks to the use of additional indicators on the module.
  • Operation taking into consideration wind direction.
  • Possibility to run and configure the RWA center with no need to program (fast and easy adjustment to building’s need without computer).

Main elements of MBZ300 center:

  • Power module.
  • Power module.
  • Drives module.
  • Detectors module.
  • Expansion module for power supply.
  • Network set.
  • Battery.